Acuvim II 5A (DIN Mount - No Display) Model- Acuvim II Series (UL, cUL, and CE Certified)
Manufacture: Accuenergy Product Description: The Accuenergy Acuvim II is a high-end multifunction power meter. It is the ideal choice for monitoring and controlling of power distribution systems. Acuvim II may be used as a data gathering device for an intelligent Power Distribution System or Plant Automation System. All monitored data is available via a digital RS485 communication port running ModbusTM Protocol. Ethernet and Profibus DP communication are also options and with new wireless technologies and protocols currently under development, the applications for the Acuvim II meter are limitless. Some of the features and electric power parameters available on the ultra-compact Acuvim II are:
True-RMS Measuring Parameter
4-Quadrant Energy
Power Quality Analysis
Over Limit Alarm
Multi Communication Ports (Eg: Ethernet, Modbus)
Web Server and Email Sending
Switch Status Monitoring
Remote Switch Controlling
Module Design (E-Module Technique)
Applications:
Metering of distribution feeders, transformers, generators, capacitor banks and motors
Medium and low voltage systems
Commercial, industrial, utility
Power quality analysis
Features: Metering
Voltage V1, V2, V3, Vlnavg, V12, V23, V31, Vllavg
Current I1, I2, I3, In, Iavg
Power P1, P2, P3, Psum
Reactive Power Q1, Q2, Q3, Qsum
Apparent Power S1, S2, S3, Ssum
Frequency F
Power Factor PF1, PF2, PF3, PF
Energy Ep_imp, Ep_exp, Ep_total, Ep_net
Reactive Energy Eq_imp, Eq_exp, Eq_total, Eq_net
Apparent Energy Es
Demand Dmd_P, Dmd_Q, Dmd_S,Dmd_I1, Dmd_I2, Dmd_I3
Load Features
Four Quadrant Powers
Monitoring
Power Quality
Voltage Harmonics 2nd to 31st and THD
Current Harmonics 2nd to 31st and THD
Voltage Crest Factor
THFF (TIF)
Current K Factor
Voltage Unbalance Factor U_unbl
Current Unbalance Factor I_unbl
Max/Min Statistics with Time Stamps
Alarms Limits can be set for up to 16 indicated parameters and can be set with a specified time interval. If any input of the indicated parameters is over or under its setting limit and persists over the specified time interval, the event will be recorded with time stamps and trigger the Alarm DO output. The 16 indicated parameters can be selected from any of the 51 parameters available. I/O option module The E-module technique was adopted for its flexibility and easy expansion of the I/O function of Acuvim II. A maximum of 3 modules can be used for one meter. Digital input, digital output, pulse output, relay output, analog input and analog output are provided by I/O option module. Communication RS485, Industry standard Modbus protocol. Module Option: Ethernet module, Profbus-DP module. Dual RS485 communication ports. Display Clear and large character LCD Screen display with white back light. Wide environmental temperature endurance. Display Load percentage, 4 quadrants power and load nature. Outline Small Size 96X96 DIN or 4" ANSI Round. Data_logging The Acuvim IIR, Acuvim IIE, model offers 4MB of onboard data logging memory to be used for historical trending. There are 3 assignable historical logs where the majority of the metering parameters can be recorded. A real time clock allows for any logged events to be accurately time stamped. Time of use User can assign up to 4 different tariffs (sharp, peak, valley and normal) to different time periods within a day according to the billing requirements. The meter will calculate and accumulate energy to different tariffs according to the meters internal clock timing and TOU settings.
Input/Output (I/O) Module Specifications: Digital Input (DI)
Input Voltage Range: 20~250 VAC/DC
Input Current (Max): 2mA
Start Voltage: 15V
Stop Voltage: 5V
Pulse Frequency (Max): 100Hz, 50% Duty Ratio (5ms ON and 5ms OFF)
SOE Resolution: 2ms
Digital Output (DO) (Photo-MOS)
Voltage Range: 0~250 VAC/DC
Load Current: 100mA (Max)
Output Frequency: 25Hz, 50% Duty Ratio (20ms ON, 20ms OFF)
Isolation Voltage: 2500V
Relay Output (RO)
Switching Voltage (Max): 250 VAC, 30VDC
Load Current: 3A
Set Time: 10ms (Max)
Contact Resistance: 100m Ohm (Max)
Isolation Voltage: 2500V
Mechanical Life: 1.5x10^7
Analog Output (AO)
Output Range: 0~5V/1~5V, 0~20mA/4~20mA (Optional)
Accuracy: 0.5%
Temperature Drift: 50ppm/degrees C typical
Isolation Voltage: 500V
Open Circuit Voltage: 15V
Analog Input (AI)
Input Range: 0~5V/1~5V, 0~20mA/4~20mA (Optional)
Accuracy: 0.2%
Temperature Drift: 50ppm/degrees C typical
Isolation Voltage: 500V
Power Supply for DI (24Vdc)
Output Voltage: 24VDC
Output Current: 42mA
Load (Max): 21DIs
Technical Specifications:
Input/Output (I/O) Module Options:
Communication Module Options:
Data Sheet Part Number: Acuvim II 5A (DIN Mount - No Display)